TPYC Shipboard Medium Voltage Power Cable
Product Description
Product Detail
FA-TPYC Shipboard Medium Voltage Power Cable application
This Cable can be applied in Marine&Offshore and various ships, ship repair and oil platforms and other offshore buildings control device and general electric lighting,machinery and equipment of factories and mines are also equally applicable.
FA-TPYC Shipboard Medium Voltage Power Cable standards
JISC 3410-1999
IEC 60092-350
IEC 60092-354
IEC 60332-1
IEC 60332-3 Cat.A(for FA-type)
Cable Model
3.6/6KV SPYCB,(FA-) SPYCB,TPYC,(FA-) TPYC
6/10KV SPYCB,(FA-) SPYCB,TPYC,(FA-) TPYC
8.7/15KV SPYCB,(FA-) SPYCBY,TPYC,(FA-) TPYC
Cable construction
FA-TPYCY Shipboard Medium Voltage Power Cable
Conductor | T(S) | Tinned annealed stranded copper, class 2 according to IEC 60228 |
Conductor screen | Semi-conducting compound | |
Insulation | P | 85°C EPR as per IEC 60092-351 |
Insulation screen | Semi-conducting compound /Tinned copper tape | |
Filler | Non-hygroscopic material (If necessary) | |
Bedding | Y | PVC,ST2 type |
Armor |
C (CB) |
Galvanized steel wire braid(-C TYPE) or copper alloy wire braid(-CB TYPE) |
Core identification | 3C Red, Yellow, Blue | |
Outer sheath color | Red |
Installations recommendations
Minimum cable bending radius
The internal radius of cable bends which are not subjected to movements by expansion, is not to be less than :
6 times the external diameter of cable
Cable which are subjected to movements by expansion and the high voltage cable are to be bent to a form of at least 12 times cable diameter.
Installations temperature
Minimum recommended temperature of installations :
-10°C Ship wiring cable with PVC sheath
-20°C Elastomeric on/off shore cables
Installations pulling force
The cable pulling force can be estimated, as a maximum limit :5Kp per mm2 conductor area in the cable.Additional tension will be supplied from the braid and the insulation and sheathing compound.